Successful system integration test of technical setup and operation of the Ecovat

EcovatEcovat demonstration site, News, Research

Image

The Ecovat energy system consists of various technical setups and is operated by software programmes developed under own management. To verify whether the setups work properly in all situations (scenarios) and whether the programmes work as they should, we have run a system integration test. We have done so in cooperation with VITO, Noda and Enexis

Step 1: testing the individual components

First, all power connected devices and appendages were individually tested. Does the right valve open and is the required notification received? Do the correct circulation pumps start running and is the heat pump or electric boiler turned on?

Step 2: testing the various operating scenarios

When everything can be operated individually, it is checked whether existing operating scenarios have been dealt with properly. The setups will be operated from the Ecovat Control Program (ECP). With the current setups there are thirty possible situations (scenarios) that can be simulated as well as checked.

Step 3: operation of the technical setups and the Ecovat by EAP

The ECP receives directions from the Ecovat Advise Program (EAP). The EAP is an algorithm that searches for an optimal efficiency of the energy system. For instance, it observes the energy market in realtime, as well as the Ecovat and the availability of the setups.

View from the doorway into the tank, the complete technical setup.


The three prefab skids in which the header section has been built. This serves as the system by means of which the five strata in the Ecovat can be operated.


The buffer tank to which the electric boilers have been connected.


Two prefab skids in which the header section has been built. This serves as the system by means of which the five strata in the Ecovat can be operated.


The control box.


SMO20 control module for the air/water heatpump and the six boilers (173 kW).